Applicable motor type | Ordinary squirrel cage AC asynchronous motor |
Rated control supply voltage | AC110V to AC220V+15% |
Supply frequency | 50/60Hz |
Rated operation voltage | Standard wiring AC380V Internal delta wiring AC380V±30% |
Nominal current | 18A~560A, 18 rated values in total |
Applicable motor | Ordinary squirrel cage AC asynchronous motor |
Start mode | Current-limited soft-start, Voltage ramp start. |
Stop mode | Free stop, Soft stop |
Logical input | Impedance 1.8 KΩ, power supply +15V |
Start frequency | Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times |
Protective function | Phase failure, overcurrent, short circuit, SCR protection, overheating, underload, phase current imbalance, wiring, internal fault, etc. |
IP degree of protection | IP00 |
Cooling system | Natural cooling or forced air cooling |
Installation type | Wall mounted-vertical installation |
Installation Environment | When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -25°C to +45°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G |
Model No. | Rated Current (A) | Applicable motor power (kW) | Size & Net weight |
CMC-008/3-MX | 18 | 7.5 | 173*275*192mm, 5.6kg |
CMC-011/3-MX | 24 | 11 | |
CMC-015/3-MX | 30 | 15 | |
CMC-018/3-MX | 39 | 18.5 | |
CMC-022/3-MX | 45 | 22 | |
CMC-030/3-MX | 60 | 30 | |
CMC-037/3-MX | 76 | 37 | |
CMC-045/3-MX | 90 | 45 | |
CMC-055/3-MX | 110 | 55 | |
CMC-075/3-MX | 150 | 75 | 285*450*305mm, 25.1kg |
CMC-090/3-MX | 180 | 90 | |
CMC-110/3-MX | 218 | 110 | |
CMC-132/3-MX | 260 | 132 | |
CMC-160/3-MX | 320 | 160 | |
CMC-185/3-MX | 370 | 185 | 320*523*330mm, 34.5kg |
CMC-220/3-MX | 440 | 220 | |
CMC-250/3-MX | 500 | 250 | |
CMC-280/3-MX | 560 | 280 |
Power range | Size (mm) | ||||||||
G | H | I | K | L | M | E | D | A/B/C | |
8 ~ 55 kW | 173 | 275 | 192 | 133 | 250 | 7 | 90 | 86 | 50 |
75 ~ 160 kW | 285 | 450 | 305 | 230 | 390 | 9 | 170 | 158 | 50 |
185 ~ 280 kW | 320 | 523 | 330 | 270 | 415 | 9 | 195 | 158 | 50 |
Load type | Initial voltage (%) | Start ramp time (s) | Stop ramp time (s) | Current limit ILIM |
Foreship propeller | 25 | 10 | 0 | 2.5 |
Centrifugal fan | 25 | 20 | 0 | 3.5 |
Centrifugal pump | 25 | 6 | 6 | 3 |
Piston compressor | 25 | 15 | 0 | 3 |
Hoisting machinery | 30 | 15 | 6 | 3.5 |
Mixer | 40 | 15 | 0 | 3.5 |
Crusher | 30 | 15 | 6 | 3.5 |
Screw compressor | 20 | 15 | 0 | 3.5 |
Spiral conveyor belt | 25 | 10 | 6 | 3.5 |
No-load motor | 25 | 10 | 0 | 2.5 |
Conveyor belt | 25 | 15 | 10 | 3.5 |
Heat pump | 25 | 15 | 6 | 3 |
Escalator | 25 | 10 | 0 | 3 |